How to use this calculator
Enter the evaporator and condenser pressures (or their saturation temperatures), the compressor efficiency, and any superheat or subcooling. Give the mass flow or the cooling load to get rates.
Formulas
Throttleh4 = h3
Compressorh2 = h1 + (h2s − h1)/ηc, s2s = s1
PerformanceCOPR = (h1 − h4)/(h2 − h1)
Worked example
Ideal cycle between 0.14 and 0.8 MPa, 0.05 kg/s of R-134a (the default; Çengel Example 11-1)
- h1 = hg at 0.14 MPa = 239.2 kJ/kg; s2 = s1 at 0.8 MPa gives h2 = 275.4 kJ/kg.
- h3 = hf at 0.8 MPa = 95.5 kJ/kg = h4.
- Q̇L = 0.05(239.2 − 95.5) = 7.18 kW, Ẇ = 0.05(275.4 − 239.2) = 1.81 kW, COP = 3.97.
Frequently asked questions
Why superheat at the compressor inlet?
A few degrees of superheat make sure no liquid droplets reach the compressor. It slightly changes the COP.
What’s the difference between COP_R and COP_HP?
A refrigerator’s useful output is the heat removed, qL; a heat pump’s is the heat delivered, qH = qL + w, so COPHP = COPR + 1.