Heat Transfer

Fin Heat Transfer Calculator

Heat rate, efficiency and effectiveness of a pin or rectangular fin.

Tool no.
ECT-F13
Rev
1.0
Updated
Oct 2026
Method
Extended-surface conduction
How to use this calculator

Choose a pin (round) or rectangular fin and enter its size and length. Pick the material to fill in the thermal conductivity, then enter the convection coefficient and the base and fluid temperatures. The tip condition sets the boundary at the free end: insulated is the usual textbook choice, convection from the tip is the most accurate, and very long applies when mL is above about 2.65.

Formulas

Fin equation and parameterd²θdx² − m²θ = 0  m = √(hPkAc)  M = √(hPkAc) θb
Heat rate by tip conditioninsulated: q = M tanh mL  very long: q = M  convective: q = M sinh mL + (h/mk) cosh mLcosh mL + (h/mk) sinh mL
Performanceηf = qh Af θb  εf = qh Ac θb  θ = T − T∞

For a pin of diameter D, Ac = πD²/4 and P = πD. For a rectangular fin of thickness t and width w, Ac = wt and P = 2(w + t). Af is the fin’s convecting surface, PL, plus the tip area Ac when the tip convects.

Worked example

A 5 mm aluminum pin, 50 mm long, in air with h = 25 W/m²·K (the default)

  1. Ac = 1.963 × 10⁻⁵ m², P = 0.01571 m, and m = √(25 × 0.01571 / (167 × 1.963 × 10⁻⁵)) = 10.94 m⁻¹.
  2. θb = 100 − 25 = 75 °C, so M = √(25 × 0.01571 × 167 × 1.963 × 10⁻⁵) × 75 = 2.691 W.
  3. mL = 0.547, so q = 2.691 × tanh 0.547 = 1.34 W.
  4. Efficiency 91.1%, effectiveness 36.4, and the tip runs at 90.0 °C.

Designing good fins

Effectiveness tells you whether a fin is worth adding: below about 2 it hardly helps. Fins work best where h is small (air, natural convection) and the material conducts well, which is why heat sinks are aluminum or copper and car radiators put fins on the air side, not the coolant side. Length has diminishing returns: tanh(mL) is already 0.76 at mL = 1 and 0.99 at mL = 2.6, so beyond that extra length only adds weight. Thin, closely spaced fins give more surface, until the gaps get so narrow that air can’t flow through them.

Assumptions and limits

  • Steady, one-dimensional conduction along the fin: the cross-section is thin enough that its temperature is uniform across it (Biot number h t/k well below 0.1).
  • Constant thermal conductivity, a uniform convection coefficient over the whole fin and no radiation.
  • The base is held at Tb. In a real heat sink, adding fins also cools the base a little.

Frequently asked questions

What is the corrected-length trick?

Use the insulated-tip formula with Lc = L + D/4 for a pin, or L + t/2 for a rectangular fin. It is a close shortcut for the convective-tip result.

Why can efficiency be high while effectiveness is low?

Efficiency compares the fin with an ideal fin at the base temperature; effectiveness compares it with having no fin. A short, thick fin is nearly isothermal (efficient) but adds little surface (not effective).

Where do I get h?

Roughly 5 to 25 W/m²·K for natural convection in air, 25 to 250 for forced air, and hundreds to thousands for liquids. The convection calculator uses h directly.